  • (a) Tanks shall have normal venting capacity sufficient to permit the filling and emptying of such tanks, plus their breathing due to temperature changes, without distortion of tank shell or roof. Tanks storing Class I and Class II flammable liquids shall be equipped where practical with either venting devices which shall be normally closed when not under pressure or vacuum, or with approved flame arresters, except that tanks under 2,500 gallons capacity for Class I liquids may have open vents.

    • Vents for emergency relief

      • (b) In addition to the provisions for normal venting herein required, every aboveground storage tank shall have some form of construction or device that will relieve excessive internal pressure, caused by exposure fires, that might cause the rupture of the tank shell or bottom. In a vertical tank, this construction may take the form of a weakened seam in the roof. Where entire dependence for such additional relief is placed upon some device other than a weak roof seam or joint, the total venting capacity of both normal and emergency vents shall be enough to prevent rupture of the shell or bottom of the tank if vertical, or of the shell or heads if horizontal.

        Such device may be a self-closing manhole cover, or one using long bolts that permits the cover to lift under internal pressure, or an additional or larger relief valve or valves.