(a) Protection from vacuum or back pressure. If the customer's equipment might create either a vacuum or a back pressure, a device must be installed to protect the system.
(b) Service regulator vents and relief vents. Service regulator vents and relief vents must terminate outdoors, and the outdoor terminal must -
(1) Be rain and insect resistant;
(2) Be located at a place where gas from the vent can escape freely into the atmosphere and away from any opening into the building; and
(3) Be protected from damage caused by submergence in areas where flooding may occur.
(c) Pits and vaults. Each pit or vault that houses a customer meter or regulator at a place where vehicular traffic is anticipated, must be able to support that traffic.