In addition to § 179.400, the individual specification requirements for the inner tank and its appurtenances are as follows:
DOT specification | 113A60W | 113C120W |
---|---|---|
Design service temperature, °F | −423 | −260. |
Material | § 179.400-5 | § 179.400-5. |
Impact test (weld and plate material) | § 179.400-5(c) | § 179.400-5(c). |
Impact test values | § 179.400-5(d) | § 179.400-5(d). |
Standard heat transfer rate. | ||
(Btu per day per lb. of water capacity, max.) (see § 179.400-4) | 0.097 | 0.4121. |
Bursting pressure, min. psig | 240 | 300. |
Minimum plate thickness shell, inches (see § 179.400-7(a)) | 3⁄16 | 3⁄16. |
Minimum head thickness, inches (see § 179.400-8 (a), (b), and (c)) | 3⁄16 | 3⁄16. |
Test pressure, psig (see § 179.400-16) | 60 | 120. |
Safety vent bursting pressure, max. psig | 60 | 120. |
Pressure relief valve start-to-discharge pressure, psig (±3 psi) | 30 | 75. |
Pressure relief valve vapor tight pressure, min. psig | 24 | 60. |
Pressure relief valve flow rating pressure, max. psig | 40 | 85. |
Alternate pressure relief valve start to-discharge pressure, psig (±3 psi) | 90. | |
Alternate pressure relief valve vapor tight pressure, min. psig | 72. | |
Alternate pressure relief valve flow rating pressure, max. psig | 100. | |
Pressure control valve Start-to-vent, max. psig (see § 179.400-20(c)(4)) | 17 | Not required. |
Relief device discharge restrictions | § 179.400-20 | 179.400-20. |
Transfer line insulation | § 179.400-17 | Not required. |
[Amdt. 179-32, 48 FR 27708, June 16, 1983, as amended at 49 FR 24318, June 12, 1984; 65 FR 58632, Sept. 29, 2000; 66 FR 45390, Aug. 28, 2001]