(a) Scope. This section provides test procedures, pursuant to the Energy Policy and Conservation Act (EPCA), as amended, which must be followed for measuring the combustion efficiency and/or thermal efficiency of a gas- or oil-fired commercial packaged boiler.
(b) Testing and Calculations. Determine the thermal efficiency or combustion efficiency of commercial packaged boilers by conducting the appropriate test procedure(s) indicated in Table 1 of this section.
Table 1 - Test Requirements for Commercial Packaged Boiler Equipment Classes
Equipment category | Subcategory | Certified rated input Btu/h |
Standards efficiency metric (§ 431.87) |
Test procedure (corresponding to standards efficiency metric required by § 431.87) |
---|---|---|---|---|
Hot Water | Gas-fired | ≥300,000 and ≤2,500,000 | Thermal Efficiency | Appendix A, Section 2. |
Hot Water | Gas-fired | >2,500,000 | Combustion Efficiency | Appendix A, Section 3. |
Hot Water | Oil-fired | ≥300,000 and ≤2,500,000 | Thermal Efficiency | Appendix A, Section 2. |
Hot Water | Oil-fired | >2,500,000 | Combustion Efficiency | Appendix A, Section 3. |
Steam | Gas-fired (all*) | ≥300,000 and ≤2,500,000 | Thermal Efficiency | Appendix A, Section 2. |
Steam | Gas-fired (all*) | >2,500,000 and ≤5,000,000 | Thermal Efficiency | Appendix A, Section 2. |
>5,000,000 | Thermal Efficiency | Appendix A, Section 2. OR Appendix A, Section 3 with Section 2.4.3.2. |
||
Steam | Oil-fired | ≥300,000 and ≤2,500,000 | Thermal Efficiency | Appendix A, Section 2. |
Steam | Oil-fired | >2,500,000 and ≤5,000,000 | Thermal Efficiency | Appendix A, Section 2. |
>5,000,000 | Thermal Efficiency | Appendix A, Section 2. OR Appendix A, Section 3. with Section 2.4.3.2. |
(c) Field Tests. The field test provisions of appendix A may be used only to test a unit of commercial packaged boiler with rated input greater than 5,000,000 Btu/h.
[81 FR 89305, Dec. 9, 2016]