(a) Low-Voltage Dry-Type Distribution Transformers.
(1) The efficiency of a low-voltage, dry-type distribution transformer manufactured on or after January 1, 2007, but before January 1, 2016, shall be no less than that required for the applicable kVA rating in the table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase | Three-phase | ||
---|---|---|---|
kVA | % | kVA | % |
15 | 97.7 | 15 | 97.0 |
25 | 98.0 | 30 | 97.5 |
37.5 | 98.2 | 45 | 97.7 |
50 | 98.3 | 75 | 98.0 |
75 | 98.5 | 112.5 | 98.2 |
100 | 98.6 | 150 | 98.3 |
167 | 98.7 | 225 | 98.5 |
250 | 98.8 | 300 | 98.6 |
333 | 98.9 | 500 | 98.7 |
750 | 98.8 | ||
1000 | 98.9 |
All efficiency values are at 35 percent per-unit load.
(2) The efficiency of a low-voltage dry-type distribution transformer manufactured on or after January 1, 2016, shall be no less than that required for their kVA rating in the table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase | Three-phase | ||
---|---|---|---|
kVA | Efficiency (%) |
kVA | Efficiency (%) |
15 | 97.70 | 15 | 97.89 |
25 | 98.00 | 30 | 98.23 |
37.5 | 98.20 | 45 | 98.40 |
50 | 98.30 | 75 | 98.60 |
75 | 98.50 | 112.5 | 98.74 |
100 | 98.60 | 150 | 98.83 |
167 | 98.70 | 225 | 98.94 |
250 | 98.80 | 300 | 99.02 |
333 | 98.90 | 500 | 99.14 |
750 | 99.23 | ||
1000 | 99.28 |
All efficiency values are at 35 percent per-unit load.
(b) Liquid-Immersed Distribution Transformers.
(1) The efficiency of a liquid-immersed distribution transformer manufactured on or after January 1, 2010, but before January 1, 2016, shall be no less than that required for their kVA rating in the table below. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase | Three-phase | ||
---|---|---|---|
kVA | Efficiency (%) |
kVA | Efficiency (%) |
10 | 98.62 | 15 | 98.36 |
15 | 98.76 | 30 | 98.62 |
25 | 98.91 | 45 | 98.76 |
37.5 | 99.01 | 75 | 98.91 |
50 | 99.08 | 112.5 | 99.01 |
75 | 99.17 | 150 | 99.08 |
100 | 99.23 | 225 | 99.17 |
167 | 99.25 | 300 | 99.23 |
250 | 99.32 | 500 | 99.25 |
333 | 99.36 | 750 | 99.32 |
500 | 99.42 | 1000 | 99.36 |
667 | 99.46 | 1500 | 99.42 |
833 | 99.49 | 2000 | 99.46 |
2500 | 99.49 |
All efficiency values are at 50 percent per-unit load.
(2) The efficiency of a liquid-immersed distribution transformer manufactured on or after January 1, 2016, shall be no less than that required for their kVA rating in the table below. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase | Three-phase | ||
---|---|---|---|
kVA | Efficiency (%) |
kVA | Efficiency (%) |
10 | 98.70 | 15 | 98.65 |
15 | 98.82 | 30 | 98.83 |
25 | 98.95 | 45 | 98.92 |
37.5 | 99.05 | 75 | 99.03 |
50 | 99.11 | 112.5 | 99.11 |
75 | 99.19 | 150 | 99.16 |
100 | 99.25 | 225 | 99.23 |
167 | 99.33 | 300 | 99.27 |
250 | 99.39 | 500 | 99.35 |
333 | 99.43 | 750 | 99.40 |
500 | 99.49 | 1000 | 99.43 |
667 | 99.52 | 1500 | 99.48 |
833 | 99.55 | 2000 | 99.51 |
2500 | 99.53 |
All efficiency values are at 50 percent per-unit load.
(c) Medium-Voltage Dry-Type Distribution Transformers.
(1) The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after January 1, 2010, but before January 1, 2016, shall be no less than that required for their kVA and BIL rating in the table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase | Three-phase | ||||||
---|---|---|---|---|---|---|---|
kVA | BIL* | kVA | BIL | ||||
20-45 kV | 46-95 kV | ≥96 kV | 20-45 kV | 46-95 kV | ≥96 kV | ||
Efficiency (%) |
Efficiency (%) |
Efficiency (%) |
Efficiency (%) |
Efficiency (%) |
Efficiency (%) |
||
15 | 98.10 | 97.86 | 15 | 97.50 | 97.18 | ||
25 | 98.33 | 98.12 | 30 | 97.90 | 97.63 | ||
37.5 | 98.49 | 98.30 | 45 | 98.10 | 97.86 | ||
50 | 98.60 | 98.42 | 75 | 98.33 | 98.12 | ||
75 | 98.73 | 98.57 | 98.53 | 112.5 | 98.49 | 98.30 | |
100 | 98.82 | 98.67 | 98.63 | 150 | 98.60 | 98.42 | |
167 | 98.96 | 98.83 | 98.80 | 225 | 98.73 | 98.57 | 98.53 |
250 | 99.07 | 98.95 | 98.91 | 300 | 98.82 | 98.67 | 98.63 |
333 | 99.14 | 99.03 | 98.99 | 500 | 98.96 | 98.83 | 98.80 |
500 | 99.22 | 99.12 | 99.09 | 750 | 99.07 | 98.95 | 98.91 |
667 | 99.27 | 99.18 | 99.15 | 1000 | 99.14 | 99.03 | 98.99 |
833 | 99.31 | 99.23 | 99.20 | 1500 | 99.22 | 99.12 | 99.09 |
2000 | 99.27 | 99.18 | 99.15 | ||||
2500 | 99.31 | 99.23 | 99.20 |
All efficiency values are at 50 percent per-unit load.
(2) The efficiency of a medium- voltage dry-type distribution transformer manufactured on or after January 1, 2016, shall be no less than that required for their kVA and BIL rating in the table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase | Three-phase | ||||||
---|---|---|---|---|---|---|---|
kVA | BIL* | kVA | BIL | ||||
20-45 kV | 46-95 kV | ≥96 kV | 20-45 kV | 46-95 kV | ≥96 kV | ||
Efficiency (%) |
Efficiency (%) |
Efficiency (%) |
Efficiency (%) |
Efficiency (%) |
Efficiency (%) |
||
15 | 98.10 | 97.86 | 15 | 97.50 | 97.18 | ||
25 | 98.33 | 98.12 | 30 | 97.90 | 97.63 | ||
37.5 | 98.49 | 98.30 | 45 | 98.10 | 97.86 | ||
50 | 98.60 | 98.42 | 75 | 98.33 | 98.13 | ||
75 | 98.73 | 98.57 | 98.53 | 112.5 | 98.52 | 98.36 | |
100 | 98.82 | 98.67 | 98.63 | 150 | 98.65 | 98.51 | |
167 | 98.96 | 98.83 | 98.80 | 225 | 98.82 | 98.69 | 98.57 |
250 | 99.07 | 98.95 | 98.91 | 300 | 98.93 | 98.81 | 98.69 |
333 | 99.14 | 99.03 | 98.99 | 500 | 99.09 | 98.99 | 98.89 |
500 | 99.22 | 99.12 | 99.09 | 750 | 99.21 | 99.12 | 99.02 |
667 | 99.27 | 99.18 | 99.15 | 1000 | 99.28 | 99.20 | 99.11 |
833 | 99.31 | 99.23 | 99.20 | 1500 | 99.37 | 99.30 | 99.21 |
2000 | 99.43 | 99.36 | 99.28 | ||||
2500 | 99.47 | 99.41 | 99.33 |
All efficiency values are at 50 percent per-unit load.
(d) Mining Distribution Transformers. [Reserved]
[78 FR 23433, Apr. 18, 2013, as amended at 86 FR 51252, Sept. 14, 2021]